N2XCH IEC 60502-1 XLPE CWS FRNC Cable

APPLICATION
Designed for fixed indoor and outdoor installations, including installation in concrete. Suitable for applications requiring low smoke emission, halogen-free properties and flame retardancy. Not suitable for direct burial in the ground or installation in water.

Construction

Conductor
RE: Class 1 solid copper
RM:: Class 2 circular stranded copper
SM: Class 2 sectorial stranded copper
Insulation
XLPE (Cross-Linked Polyethylene)
Inner Sheath
Halogen-free compound
Concentric Conductor
Copper wires with counter helix of copper tape
Sheath
LSZH (Low Smoke Zero Halogen)
Core Identification
2 core:  Brown  Blue
3 core: Brown  Black  Grey
4 core: Blue  Brown  Black  Grey
5 core: Black  Blue  Brown  Black  Grey
Sheath Colour
Black

Technical Features

Voltage Rating Uo/U
0.6/1kV
Temperature Rating
Fixed: -30°C to +90°C
Minimum Bending Radius
15 x overall diameter

Standard

EC 60502-1 VDE 0276 Part 604,
Flame Retardant according to IEC/EN 60332-3-24
Low Smoke Zero Halogen according to IEC/EN
60754-1/2, IEC/EN 61034-1/2

Technical Data

NO. OF
CORES
CONDUCTOR
TYPE
CONDUCTOR NOMINAL CROSS
SECTIONAL AREA
mm2
CONCENTRIC CONDUCTOR
CROSS SECTION
mm2
NOMINAL THICKNESS
OF INSULATION
mm
NOMINAL OVERALL
DIAMETER
mm
NOMINAL
WEIGHT
kg/km
2RE1.51.50.712250
2RE2.52.50.712280
2RE440.714320
2RE660.715410
2RE10100.717550
2RE16160.719780
3RE1.51.50.712250
3RE2.52.50.713320
3RE440.714400
3RE660.716500
3RE10100.718750
3RE16160.7211000
3RM25160.9241600
3SM35160.9271900
3SMv50251302400
3SMv70351.1342615
3SMv95501.138.13636
3SMv120701.242.54606
3SMv150701.4475552
3SMv185951.6506680
3SMv2401201.757.18964
4RE1.51.50.713235
4RE2.52.50.714302
4RE440.715411
4RE660.717527
4RE10100.719762
4RE16160.7221139
4RM25160.9271634
4SM35160.9292080
4SMv50251332790
4SMv70351.1413550
4SMv95501.1464800
4SMv120701.2506556
4SMv150701.4557904
4SMv185951.6629950
4SMv2401201.76812912
5RE1.51.50.714283
7RE1.52.50.716380
7RE2.52.50.718480
7RE440.719650
7RE660.720850
10RE2.540.718550
12RE1.52.50.720550
12RE2.540.721750
14RE1.52.50.717.6486
21RE2.5100.7231050
24RE1.560.725950
24ER2.5100.7261106
30RE1.560.7271100
30RE2.560.7281500

N2XCH IEC 60502-1 XLPE CWS FRNC Cable

N2XCH IEC 60502-1 Cable features XLPE insulation, copper wire screening and a flame-retardant, halogen-free sheath, providing low smoke emission and reduced corrosive gas release in the event of fire. Designed for fixed indoor and outdoor installations, it is suitable for commercial buildings, industrial facilities and infrastructure projects.

Learn more about international industrial cable criteria on Wikipedia.
You can also check our full Cable Products List to find more armored and screened solutions.